Shanghai Zhiyue Electric Co., Ltd    021-53080810   a65148373@163.com
China Zhiyue

Relay

JR36-63 Thermal overload relay
  • JR36-63 Thermal overload relay

JR36-63 Thermal overload relay

1. Altitude: no more than 2000m;
2. Ambient temperature: -50°C~+40°C, the average value of 24h does not exceed 35°C;
3. Relative humidity: no more than 50% when the highest temperature is +40°C, the maximum The relative humidity is 90% (20°C). Special measures must be taken for condensation on the product due to temperature changes;
4. Pollution level: Level 3;

Detailed introduction

JR36-63 Thermal overload relay

JR36-63 Thermal overload relay

Main purpose and scope of application
JR36 series bimetallic thermal overload relay (hereinafter referred to as thermal relay), suitable for AC 50Hz, working voltage to 690V, current 0.25A~160A long-term work or intermittent long-term work of general AC motor overload and Lack of phase protection can also be used for capacitor overload protection. The relay has overload and lack of phase protection, temperature compensation, action flexibility check, manual reset and automatic reset, it is a new generation of ideal products to replace JRl6B series.
Products comply with standards such as GB14048.4, GB14048.5, IEC60947-4-1 and IEC60947-5-1.

Model and meaning

Working conditions
1. Altitude: no more than 2000m;
2. Ambient temperature: -50°C~+40°C, the average value of 24h does not exceed 35°C;
3. Relative humidity: no more than 50% when the highest temperature is +40°C , The maximum relative humidity is 90% (20℃). Special measures must be taken for condensation on the product due to temperature changes;
4. Pollution level: 3;
5. The installation tilt angle between the installation surface and the vertical surface should not exceed ±5°, and there should be no significant vibration and impact at the installation site ;
6, the main circuit using the basic categories AC-3, AC-15 auxiliary circuit or DC-13, the operating frequency (average) 15 / h.

Structural features
In addition to overload protection and phase loss protection, this relay also has the following structural features: 1. Temperature compensation structure;
2. Action flexibility check;
3. Convertible manual reset or automatic reset device;
4. Manual A device that disconnects normally closed contacts.

Product model and specifications
The setting current and adjustment range of the thermal relay are shown in the table below.

Thermal relay model Rated working current A Thermal element grade
JR36-20 20 Rated current of heating element A Current adjustment range A Equipped capacitor
0.35 0.25~0.35 -
0.5 0.32~0.5 -
0.72 0.45~0.72 -
1.1 0.68~1.1 -
1.6 1~1.6 -
2.4 1.5~2.4 -
3.5 2.2~3.5 ≤1kvar
5 3.2~5 ≤2kvar
7.2 4.5~7.2 ≤3kvar
11 6.8~11 ≤5kvar
16 10~16 ≤7.5kvar
twenty two 14~22 ≤10kvar
JR36-32 32 32 20~32 ≤15kvar
JR36-63 63 twenty two 14~22 ≤10kvar
32 20~32 ≤15kvar
45 28~45 ≤20kvar
63 40~63 ≤30kvar
JR36-160 160 63 40~63 ≤30kvar
85 53~85 ≤40kvar
120 75~120 ≤55kvar
160 100~160 ≤75kvar

Note: If JR36 series thermal overload relay is used as overcurrent protection of capacitor (0.4kV~0.45kV), please refer to the column of "equipped capacitor" for selection; if used for motor or other equipment protection, please select according to current specifications type.

The main technical parameters and
auxiliary contact technical parameters are shown in the table below

Rated insulation voltage (Ui) V 380
Conventional heating current (Ith) A 5
Rated working current at 380V (le)A 0.47

Serial number

Setting current multiple

Action time

Starting condition

Ambient air temperature

1

1.05

No action within 2h

Cold start

 

2

1.2

Action within 2h

 

Hot state (after the serial number 1 test) start

 

20℃±5℃

 

3

 

1.5

10A

2min

10

10A

4min 2s<Tp≤10s

 

4

 

7.2

 

Cold start

 

10

4s<Tp≤10s

 The action characteristics of the three-phase thermal relay with phase loss protection when the load of each phase is unbalanced meet the requirements of the following table.

Serial number Setting current multiple Action time Starting condition Ambient air temperature
Any two phase Another phase
1 1 0.9 No action within 2h Cold start  
2 1.15 0 Action within 2h Hot state (after the serial number 1 test) start 20℃±5℃

The temperature compensation performance of the thermal relay conforms to the following table.

Serial number Setting current multiple Action time Starting condition Ambient air temperature
1 1 No action within 2h Cold start 40℃±2℃
2 1.2 Action within 2h Hot state (after the serial number 1 test) starts
3 1.05 No action within 2h Cold start -5℃±2℃
4 1.3 Action within 2h Hot state (after the serial number 3 test) starts

The tripping characteristic curve is shown in the figure below.

1 Balanced operation. 3-phase, starting from the cold state.
2 Balanced operation, 2 phases, starting from cold state.
3 Balanced operation, 3 phases, starting from the hot state.

Instructions
for use 1. In order to make the setting current of the thermal relay match the rated current of the load, you can turn the adjusting knob to align the required current value with the white arrow. There may be some error between the current value on the knob and the setting current value. In actual use, it is slightly deflected according to the situation. If you need to set the current value between the two scales, you can turn the adjusting knob proportionally and adjust it appropriately in actual use.
2. The thermal relay is adjusted to the automatic reset mode when leaving the factory. If you want to adjust to manual reset, you can reverse the screw in the side hole of the thermal relay about three or four turns.

Outline and installation dimensions
JR36-20 JR36-32 thermal overload relay outline and installation dimensions

 

Outline and installation dimensions of JR36-63 thermal overload relay

Outline and installation dimensions of JR36-160 thermal overload relay

Ordering instructions
1. When ordering, the model, name, rated operating current, thermal element setting current range and order quantity should be indicated. For example: 20 sets of JR36-20 thermal relays with rated current of 5A.
2. When the product leaves the factory, the main circuit and auxiliary circuit terminals are not equipped with protective covers. If the user needs, please explain to the manufacturer.

Message Feedback

If you have any enquiry about quotation or cooperation,please free to email us ata65148373@163.comor use the following enquiry form,Our sales representative will contact you within 24 hous.thank you for your interest in our products.

Get to know Us Better Now!

Share our Product over the Social Networks

Search!

Search across our website

主站蜘蛛池模板: 无码人妻丰满熟妇A片护士M| 短篇H爽文小说集大全| 97国内免费久久久久久久久久| 亚洲 欧美 日韩 综合aⅴ视频| 免费又黄又爽A片免费看漫画| 国内精品人妻无码久久久影院蜜桃 | 波多野结衣hd系列在线播放 | 国产在线高清一级毛片| 国产成人精品男人免费| 中文字幕视频在线区一区二| 日产日韩亚洲欧美综合搜索| 久久国产中文娱乐网| 国产成人精品一区二区| 真人性做爰无遮A片免费| 人妻无码ⅴ中文字幕日韩| 精品成人日韩欧美软件| 东京热av人妻无码专区| 亚洲欧美日韩精品在线| 欧美夫妻性生活| 国产偷v国产偷v亚洲高清| AV永久综合在线观看尤物| 无码成人精品区在线观看| 久久久久久久精品成人热小说| 国产精品1024香蕉在线观看| 18禁成人黄网站免费观看| 人妻少妇一区二区三区| 国产中文字幕永久在线观看| 波多野结衣久| 四虎无码永久在线影库网址一个人 | 无码aⅴ免费一区二区三区 | 国产一区日本二区欧美三区| 不卡无在一区二区三区四区| 无人区乱码一线二线久久久久 | 视频一区二区三区日韩欧美| 欧美日韩国产中文字幕在线| 国产三级在线影音先锋国产精品| 99精品国产在热久久| 日韩福利视频一区| 国精产品999国精产品官网| a级毛片一区二区免费视频 | 免费看成人做爰片|